How to change ``GATT`` Gas Attenuator to Neon ============================================= 1. From the SASE3 Photon Beam Transport ``SA3_MAIN`` main panel, open the SASE3 Gas Attenuator. .. image:: SA3_MAIN.svg :width: 50% :align: left #. From the SASE3 Gas Attenuator ``G_ATT_03`` main panel, click on ``Pause Injection`` (not Stop injection). The ``Process Status`` on top will changed to ``PAUSED``. Then open the SASE3 Gas Attenuator System Setup ``G_ATT_01`` panel by clicking on ``01 - System Settings/Pset= f(Attenuation)``. .. image:: G_ATT_03.svg :width: 50% :align: left #. From the SASE Gas Attenuator System Set-Up ``G_ATT_01`` panel, open the Central Gas Injection Module Control panel ``G_ATT_CGI`` panel by clicking on ``CGI Module Control Panel``. .. image:: G_ATT_01.svg :width: 50% :align: left #. From the Central Gas Injection Module Control panel ``G_ATT_CGI`` panel, open the Extended panel by clicking on ``Extended Panel``. .. image:: G_ATT_CGI.svg :width: 50% :align: left #. In the Extended Panel ``G_ATT - CGI Extended`` one can see the Gas Manifold with 5 different incoming gas lines consisting of 2 large gas line, Ar and N2, and 3 minican gas line. .. image:: G_ATT_CGI_Extended.svg :width: 50% :align: left Labels of the minican gas line are not necessarily correct and one needs to know which minican gas line is the Neon gas line. The pressure indicates if minican is empty. a. Switch ``N2 Mode`` to ``Off``. #. Switch ``Ne Mode`` to ``On`` if this is the right minican. #. Evacuate the gas manifold by switch on the membrane pump and opening the valve at the bottom of the gas manifold. #. Pump down the gas manifold for 3 to 5 minutes. #. Switch off the membrane pump. It will automatically switch off the valve. #. Open the Ne valve. #. From the Central Gas Injection Module Control panel ``G_ATT_CGI`` panel, select the adequate shutoff valve according to the orifice size. .. image:: G_ATT_CGI.svg :width: 50% :align: left a. Set ``Control Mode`` to be ``1``. #. Select the ``Analog S.P. (set)`` to a value between 4.5 to 14 mA. Below 4.0 mA the shutoff valve should remain closed. The maximum opening is obtained for a value of 20 mA. #. Regulate the Analog S.P. to get the right Neon absorption in the spectrum. Switch to a different shutoff valve orifice size if the value goes outside the range of 4.5 to 14mA with the current orifice size. How to change ``GATT`` Gas Attenuator back to N2 with 2mbar =========================================================== #. From the Central Gas Injection Module Control panel ``G_ATT_CGI`` panel, set the ``Analog S.P. (set)`` of the currently used shutoff valve to 0 to close it. Then close Shutoff valve. .. image:: G_ATT_CGI.svg :width: 50% :align: left #. From the Extended Panel ``G_ATT - CGI Extended``, switch the currently used minican ``Ne Mode`` to ``Off`` and switch the 'N2 Mode' to 'On'. .. image:: G_ATT_CGI_Extended.svg :width: 50% :align: left #. Use the ``Automatic GAS Exchange`` to ``On`` and click on ``PumpPurgetoN2``. This procedure will pump down and purge the gas manifold a few times. The procedure takes about 15 min. Wait for the N2 exchange to be finished as indicated in the status box below. #. Switch ``Automatic Gas Exchange`` to ``Off``. #. From the SASE3 Gas Attenuator ``G_ATT_03`` main panel, go to 2mbar. .. image:: G_ATT_03.svg :width: 50% :align: left