BeckhoffEbaraRoots

Commands

Key Displayed Name Description Alias Access Level Allowed States
off Off
Switch off device
COff OPERATOR CHANGING, ON, ERROR, RUNNING, INTERLOCK_BROKEN
on On
Switch on main pump
COn OPERATOR OFF, INTERLOCK_BROKEN
pumpReset Pump Reset
send a reset signal to the pump
CReset OPERATOR  
boostOff Boost Off
Turn the booster pump off. This functionality
can only be used when DIP switch A-8 has been
set to On. (Default is Off)
COffBoost EXPERT STARTING, ON, ERROR, RUNNING, INTERLOCK_BROKEN
boostOn Boost On
Turn the booster pump on. This functionality
can only be used when DIP switch A-8 has been
set to On. (Default is Off)
COnBoost EXPERT ON, RUNNING, INTERLOCK_BROKEN
energySavingModeOff Energy Saving Mode Off
Energy Saving mode is deactivated.
CEnergySavingModeOff EXPERT ON, RUNNING, INTERLOCK_BROKEN
energySavingModeOn Energy Saving Mode On
Energy Saving mode is activated. This mode runs
the main and booster pumps at a slower pre-
defined speed as cofigured via the device
interface.
CEnergySavingModeOn EXPERT ON, RUNNING, INTERLOCK_BROKEN

Properties

Key Displayed Name Description Alias Type Access Level Access Mode Allowed States
isAlarm Pump Alarm
Device is in alarm state
  Bool OBSERVER READONLY  
isBoosterPumpOn Booster pump is on
Booster pump is on
  Bool OBSERVER READONLY  
isBoosterPumpRunning Booster pump is running
Booster pump is running
  Bool OBSERVER READONLY  
isEmergencyStop Emergency Stop
Emergency Stop active
  Bool OBSERVER READONLY  
isEnergySavingOn Energy Saving Mode On
Energy saving mode actually on
  Bool OBSERVER READONLY  
isEnergySavingSet Energy Saving Mode Set
Energy saving mode wanted on
  Bool OBSERVER READONLY  
isLocalMode Local Mode
Device in local mode (remote control disabled)
  Bool OBSERVER READONLY  
isMainPumpOn Main pump is on
Main pump is on
  Bool OBSERVER READONLY  
isMainPumpRunning Main pump is running
Main pump is running
  Bool OBSERVER READONLY  
isN2Warning N2 Warning
Device is in has N2 warning
  Bool OBSERVER READONLY  
isReset Reset alarms on the device
reset for tripped alarms or alarms and warnings
on the device
  Bool OBSERVER READONLY  
isStarting pump starting
True when pump is starting
  Bool OBSERVER READONLY  
isWarning Pump Warning
Device is in a warning state
  Bool OBSERVER READONLY  
backPressure Back Pressure
Back Pressure in kPa
ABackPressure Float OPERATOR READONLY  
coolingWaterFlow Cooling water flow
Cooling water flow in l/min
ACoolingWaterFlow Float OPERATOR READONLY  
motCasingTemp Casing temperature
Main Pump Motor casing temperature
AMotCasingTemp UInt32 OPERATOR READONLY  
motorSpeedBp Booster Pump Motor Speed
Booster Pump Power in K/min
AMotorSpeedBP Float OPERATOR READONLY  
motorSpeedMp Main Pump Motor Speed
Main pump motor speed in K/min
AMotorSpeedMP Float OPERATOR READONLY  
powerBp Boost Pump Power
Booster Pump Power in kW
APowerBP Float OPERATOR READONLY  
powerMp Main Pump Power
Main Pump Power in kW
APowerMP Float OPERATOR READONLY  
pumpN2Flow Pump N2 Flow
Pump N2 Flow in Pa*m^3/s
APumpN2Flow Float OPERATOR READONLY  
pumpRunTime Pump run time
Total run time of the pump in hours
APumpRunTime UInt32 OPERATOR READONLY  
warningOrErrors Warning or Errors
True if any warning or error is present
AWarningOrErrors UInt32 OPERATOR READONLY  
baudRate baudRate

ABaudRate UInt8 EXPERT RECONFIGURABLE  
dataFrame dataFrame

ADataFrame UInt8 EXPERT RECONFIGURABLE  
enableCtsRts enableCtsRts

AEnableCTSRTS Bool EXPERT READONLY  
enableXonXoffRx enableXonXoffRx

AEnableXOnXOffRx Bool EXPERT READONLY  
enableXonXoffTx enableXonXoffTx

AEnableXOnXOffTx Bool EXPERT READONLY  
rxBufferFull rxBufferFull

ARxBufferFull UInt16 EXPERT RECONFIGURABLE  
sendFifoDataCont sendFifoDataCont

ASendFIFODataCont UInt8 EXPERT RECONFIGURABLE  
transferRateOpt transferRateOpt

ATransferRateOpt Bool EXPERT READONLY