BeckhoffBronkhorst¶
Commands¶
Key | Displayed Name | Description | Alias | Access Level | Allowed States |
---|---|---|---|---|---|
softReset | Soft Reset | Soft
Reset
|
USER |
Properties¶
Key | Displayed Name | Description | Alias | Type | Access Level | Access Mode | Allowed States |
---|---|---|---|---|---|---|---|
IOStatus | IO Status | AIOStatus | UInt8 | EXPERT | RECONFIGURABLE | ||
PIDKp | PID Kp | PID factor Kp
|
APIDKp | Float | EXPERT | RECONFIGURABLE | |
PIDTd | PID Td | PID factor Td
|
APIDTd | Float | EXPERT | RECONFIGURABLE | |
PIDTi | PID Ti | PID factor Ti
|
APIDTi | Float | EXPERT | RECONFIGURABLE | |
analogInFullScale | Analog Input Full Scale | Analog Input correction factor full scale (2000
a.u. = 1 V * Multiplication)
|
AAnalogInputFullScale | Int16 | EXPERT | RECONFIGURABLE | |
analogInZeroScale | Analog Input Zero Scale | Analog Input correction factor zero scale
|
AAnalogInputZeroScale | Int16 | EXPERT | RECONFIGURABLE | |
analogInput | Analog Input | Measurement expressed in arbitrary units 32000
is 100%
|
AAnalogInput | Int16 | EXPERT | READONLY | |
analogOutFullScale | Analog Output Full Scale | Analog Output correction factor full scale
(2000 a.u. = 1 V * Multiplication)
|
AAnalogOutputFullScale | Int16 | EXPERT | RECONFIGURABLE | |
analogOutZeroScale | Analog Output Zero Scale | Analog Output correction factor zero scale
|
AAnalogOutputZeroScale | Int16 | EXPERT | RECONFIGURABLE | |
analogSetPointFullScale | Analog Setpoint Full Scale | analog setpoint output correction factor full
scale (2000=1*multiplication)
|
AAnSetpntInputFullScale | Int16 | EXPERT | RECONFIGURABLE | |
analogSetPointZeroScale | Analog Setpoint Zero Scale | analog V ref. input corr. factor zero scale
(DSCM-A 0=0 other 32767=0)
|
AAnSetpntInputZeroScale | Int16 | EXPERT | RECONFIGURABLE | |
calibrationCertificate | Calibration Certificate | Number of calibration certificate (last basic
calibration)
|
ACalibrationCertificate | String | EXPERT | RECONFIGURABLE | |
calibrationDate | Calibration Date | Date of last (basic) calibration (e.g.
19991231)
|
ACalibrationDate | String | EXPERT | RECONFIGURABLE | |
calibrationMode | Calibration Mode | Calibration Mode : 0=(idle: no action) 1=(adc
self calibration) 2=(dmfc) 3=(dmfc) 4=(dmfc)
5=(dmfc) 6=(dmfc) )7=(dmfc) 8=(dmfc)
)9=(customer zero) 10=(adjust Vref output by
connecting it to analog in) 11=(adjust analog
out by connecting it to analog in) 12=(adjust
valveoutput by connecting it to analog in)
13=(dmfc) 14=(dmfc) 15=(analog output = 0 %)
16=(analog output = 100 %) 17=(analog output =
50 %) 18=(factory zero) 19=(sensor
differentiator (setpoint steps are needed!))
20=(automatic sensor configuration) 21=(sensor
temperature calibration) 22=(customer zero (no
control mode 9 needed)) 255=(Error mode (result
of previous cal mode))
|
ACalibrationMode | UInt8 | EXPERT | RECONFIGURABLE | |
capacity | Capacity | Capacity
|
ACapacity | Float | EXPERT | RECONFIGURABLE | |
capacity0Percent | Capacity 0 Percent | capacity 0 Percent
|
ACapacity0Percent | Float | EXPERT | RECONFIGURABLE | |
capacityUnit | Capacity unit | Capacity unit
|
ACapacityUnit | String | EXPERT | READONLY | |
capacityUnitIndex | capacityUnitIndex | ACapacityUnitIndex | UInt8 | EXPERT | RECONFIGURABLE | ||
comm.baudRate | Baud Rate | Baud Rate: 1=300 2=600 3=1200 4=2400 5=4800
6=9600 7=19200 8=38400 9=57600 10=115200 Baud.
|
ABaudRate | UInt8 | EXPERT | RECONFIGURABLE | |
comm.bufferFull | Buffer Full | Buffer Full Notification.
|
ARxBufferFull | Int16 | EXPERT | RECONFIGURABLE | |
comm.dataFrame | Data Frame | Data Frame: 1=7E1 2=7O1 3=8N1 4=8E1 5=8O1 9=7E2
10=7O2 11=8N2 12=8E2 13=8O2.
|
ADataFrame | UInt8 | EXPERT | RECONFIGURABLE | |
comm.enableRtsCts | Enable RTS/CTS | Enable RTS/CTS
|
AEnableCTSRTS | Bool | EXPERT | RECONFIGURABLE | |
comm.enableXonXoffRx | Enable XOn/XOff Rx | Enable XOn/XOff supported rx data
|
AEnableXOnXOffRx | Bool | EXPERT | RECONFIGURABLE | |
comm.enableXonXoffTx | Enable XOn/XOff Tx | Enable XOn/XOff supported tx data
|
AEnableXOnXOffTx | Bool | EXPERT | RECONFIGURABLE | |
comm.resetUnitDummy | resetDummy(do not touch) | please do not touch this value
|
AResetUnit | UInt8 | EXPERT | RECONFIGURABLE | |
comm.serialCheck | Serial Check | Check serial protocol command value (reads back
string from command function window (ASerP
input value)
|
ASerCheck | String | EXPERT | RECONFIGURABLE | |
comm.serialStartCharacter | Start Character | Serial message start character.
|
ASTX0 | Char | EXPERT | RECONFIGURABLE | |
comm.serialStopCharacter | Stop Character | Serial message stop character.
|
AETX0 | Char | EXPERT | RECONFIGURABLE | |
controlMode | Control Mode | Control Mode Selection 0=(setpoint = BUS
setpoint) 1=(setpoint = analog input)
2=(setpoint = master output(FLOW-BUS) * slave
factor(FLOW-BUS)) 3=(close valve) 4=(controller
idle (no reaction on changes in sensor signal))
5=(testmode enable (select subject with par
70)) 6=(tuningmode enable (select subtject with
par 79)) 7=(setpoint = 100%) 8=(purge valve
(fully open)) 9=(calibration mode enable
(select subject with par 58)) 10=(setpoint =
master output(analog in) * slave factor(FLOW-
BUS)) 11=(setpoint = keyboard OR FLOW-BUS
setpoint) 12=(setpoint = 0%) 13=(setpoint =
master output(FLOW-BUS) * slave factor(analog
in)) 14=((FPP) Range select mode) 15=((FPP)
Manual start sensor select, automatic end
sensor) 16=((FPP) Automatic start sensor
select, manual end sensor) 17=((FPP) Automatic
start and end sensor) 18=(setpoint = RS232
setpoint) 19=(RS232 broadcast mode) 20=(valve
stearing (valve = setpoint)) 21=(analog valve
stearing (valve = analog setpoint)) 22=(valve
safe state)
|
ACtrlMode | UInt8 | EXPERT | RECONFIGURABLE | |
customerModel | Customer Model | Customer Model
|
ACustomerModel | String | EXPERT | READONLY | |
density | Density | Density of selected fluid in kg/m3
|
ADensity | Float | EXPERT | RECONFIGURABLE | |
enableFifoCont | Enable FIFO Cont. | Enable send FIFO data continuous
|
AFifoCont | Bool | EXPERT | RECONFIGURABLE | |
enableTransferOpt | Enable Transfer Rate Opt. | Enable transfer rate optimization
|
ATransferOpt | Bool | EXPERT | READONLY | |
fSetpoint | F set point | f set point
|
AfSetpoint | Float | EXPERT | RECONFIGURABLE | |
firmwareId | Firmware ID | Firmware Identification number
|
AFirmwareID | UInt8 | EXPERT | READONLY | |
firmwareVersion | Firmware Version | Firmware Version
|
AFirmwareVersion | String | EXPERT | READONLY | |
fluidName | Fluid Name | Fluid Name
|
AFluidName | String | EXPERT | RECONFIGURABLE | |
fluidNumber | Fluid Number | Fluid Number
|
AFluidNumber | UInt8 | EXPERT | RECONFIGURABLE | |
massFlow | Mass flow | mass flow kg/min
|
AMassFlow | Float | EXPERT | READONLY | |
measure | Measure | Measured value (100% = 32000)
|
AMeasure | Int16 | EXPERT | RECONFIGURABLE | |
measurementStatus | Measurement Status | Measurement status
|
AMeasurementStatus | Int16 | EXPERT | READONLY | |
orifice | Orifice | orifice diameter
|
AOrifice | Float | EXPERT | RECONFIGURABLE | |
pIOparamCapacity0 | APIOparamCapacity0 | PIO param Capacity 0
|
APIOparamCapacity0 | Float | EXPERT | RECONFIGURABLE | |
pIOparamCapacity100 | APIOparamCapacity100 | PIO param Capacity 100
|
APIOparamCapacity100 | Float | EXPERT | RECONFIGURABLE | |
powerMode | Power Mode | APowerMode | UInt8 | EXPERT | RECONFIGURABLE | ||
pressure | Pressure | Pressure
|
APressure | Float | EXPERT | RECONFIGURABLE | |
pressureSensorType | Pressure Sensor Type | Pressure Sensor Type : 0=(delta-P 0..5” W.C.)
1=(delta-P 0…10” W.C.) 2=(absolute pressure
800-1200 mbar) 3=(absolute pressure 800-1100
mbar) 4=(delta-P -5…0” W.C.) 5=(delta-P
-10…0” W.C.) 6=(delta-P -10…+10” W.C.)
7=(delta-P 0…1 PSI) 8=(delta-P -1…0 PSI)
10=(absolute pressure 0-10 bar)
|
APressureSensorType | UInt8 | EXPERT | RECONFIGURABLE | |
referenceVoltageFullScale | Reference Voltage Full Scale | analog V ref. input correction factor full
scale (2000=1*multiplication)
|
ARefVoltInputFullScale | Int16 | EXPERT | RECONFIGURABLE | |
referenceVoltageZeroScale | Reference Voltage Zero Scale | analog V ref. input corr. factor zero scale
(DSCM-A 0=0 other 32767=0)
|
ARefVoltInputZeroScale | Int16 | EXPERT | RECONFIGURABLE | |
resetInputSelection | Reset Input Selection | Reset Input Selection
|
AResetInputSelection | String | EXPERT | RECONFIGURABLE | |
sensorInputFullScale | Sensor Input Full Scale | analog sensor signal input correction factor
full scale (2000=1*multiplication)
|
ASensorInputFullScale | Int16 | EXPERT | RECONFIGURABLE | |
sensorInputZeroScale | Sensor Input Zero Scale | analog sensor signal input corr. factor zero
scale (DSCM-A 0=0 other 32767=0)
|
ASensorInputZeroScale | Int16 | EXPERT | RECONFIGURABLE | |
sensorNumber | Sensor Number | pointer to sensor number in calibration tube
(FPP)
|
ASensorNumber | UInt8 | EXPERT | RECONFIGURABLE | |
sensorType | Sensor Type | Sensor Type 0=(pressure (controller))
1=(liquid volume (controller)) 2=(liquid/gas
mass (controller)) 3=(gas volume (controller))
4=(other sensor type (controller))
128=(pressure (sensor)) 129=(liquid volume
(sensor)) 130=(liquid/gas mass (sensor))
131=(gas volume (sensor)) 132=(other sensor
type (sensor))
|
ASensorType | UInt8 | EXPERT | RECONFIGURABLE | |
serialCommand | Serial Command | Send serial protocol command.
|
ASerial | String | EXPERT | RECONFIGURABLE | |
serialNumber | Serial Number | Serial Number
|
ASerialNumber | String | EXPERT | READONLY | |
serviceDate | Service Date | Date of last service action
|
AServiceDate | String | EXPERT | RECONFIGURABLE | |
serviceNumber | Service Number | AServiceNumber | String | EXPERT | RECONFIGURABLE | ||
setPoint | Set Point | Set Point (100% = 32000)
|
ASetpoint | Int16 | EXPERT | RECONFIGURABLE | |
temperature | Temperature | Temperature
|
ATemperature | Float | EXPERT | RECONFIGURABLE | |
time | Time | Time, maybe uptime, HW documentation unclear.
|
ATime | Float | EXPERT | RECONFIGURABLE | |
tuningMode | Tuning Mode | Tuning Mode: 0=(idle; no action) 1=(sensor)
2=(valve) 3=(Fuzzy controller normal
operation) 4=(Fuzzy controller open at zero)
5=(PID controller)
|
ATuningMode | UInt8 | EXPERT | RECONFIGURABLE | |
resetManually | reset | Write this property to Reset: 0=(no reset)
1=(reset counter value (no mode change) or
common reset) 2=(reset alarm) 3=(restart
batch counter) 4=(reset counter value (counter
off)) 5=(Reset module (soft reset))
|
AReset | UInt8 | ADMIN | RECONFIGURABLE |