BeckhoffPfeifferTCDriveUnit¶
Commands¶
Key | Displayed Name | Description | Alias | Access Level | Allowed States |
---|---|---|---|---|---|
disablePumpingStation | Disable Pumping Station | Disables the pumping station
|
COff | USER | STOPPED, INTERLOCK_BROKEN |
enablePumpingStation | Enable Pumping Station | Enables the pumping station (does not start
pumping yet)
|
COn | USER | OFF, STOPPED, INTERLOCK_BROKEN |
startPumping | Start Pumping | Starts the pump
|
CPump | USER | STOPPED, INTERLOCK_BROKEN |
stopPumping | Stop Pumping | Stops the pump
|
CStop | USER | STARTED, INTERLOCK_BROKEN |
remotePriorityOff | Remote Priority Off | Disable remote control
|
CRemotePriorityOff | EXPERT | STOPPED, STARTED, ERROR, OFF, INTERLOCK_BROKEN |
remotePriorityOn | Remote Priority On | Enable remote control
|
CRemotePriorityOn | EXPERT | STOPPED, STARTED, DISABLED, ERROR, OFF, INTERLOCK_BROKEN |
resetController | Reset Controller Error | reset error on controller
|
CResetCtrl | EXPERT | ERROR, INTERLOCK_BROKEN |
startHeating | Start Heating | Start Heating
|
CHeat | EXPERT | STOPPED, STARTED, INTERLOCK_BROKEN |
startStandby | Start Standby | Start Standby operation
|
CStandby | EXPERT | STOPPED, STARTED, INTERLOCK_BROKEN |
startVenting | Start Venting | Start Venting
|
CVenting | EXPERT | STOPPED, STARTED, INTERLOCK_BROKEN |
stopHeating | Stop Heating | Stop Heating
|
CStopHeat | EXPERT | STOPPED, STARTED, INTERLOCK_BROKEN |
stopStandby | Stop Standby | Stop Standby operation
|
CStopStandby | EXPERT | STOPPED, STARTED, INTERLOCK_BROKEN |
stopVenting | Stop Heating | Stop Heating
|
CStopVenting | EXPERT | STOPPED, STARTED, INTERLOCK_BROKEN |
Properties¶
Key | Displayed Name | Description | Alias | Type | Access Level | Access Mode | Allowed States |
---|---|---|---|---|---|---|---|
isRPMExceed | isRPMExceed | isRPMExceed
|
Bool | OBSERVER | READONLY | ||
remotePriority | Remote Priority | Remote priority.
|
ARemotePriority | Bool | OBSERVER | READONLY | |
standbyOnOff | Standby On/Off | Standby On/Off.
|
AStandby | Bool | OBSERVER | READONLY | |
actualRotationSpeed | Actual Rot. Speed | Actual rotation speed.
|
AActualRotSpeed | UInt32 | OPERATOR | READONLY | |
actualRotationSpeedRpm | Actual Rot. Speed | Actual rotation speed [rpm].
|
AActualRotSpeedrpm | UInt32 | OPERATOR | READONLY | |
driveCurrent | Drive Current | Drive current.
|
ADriveCurrent | Float | OPERATOR | READONLY | |
driveVoltage | Drive Voltage | Drive voltage.
|
ADriveVoltage | Float | OPERATOR | READONLY | |
errorCode | Error Code | Error code.
|
AErrorCode | String | OPERATOR | READONLY | |
temperatureBearing | Temp Bearing | Temperature bearing.
|
ATemperatureBearing | UInt32 | OPERATOR | READONLY | |
temperatureElectronic | Temp Electronics | Temperature electronics.
|
ATemperatureElectronic | UInt32 | OPERATOR | READONLY | |
temperatureMotor | Temp Motor | Temperature motor.
|
ATemperatureMotor | UInt32 | OPERATOR | READONLY | |
acceleration | Acceleration | Acceleration [rpm/s].
|
AAcceleration | UInt32 | EXPERT | READONLY | |
accessoryConnectionA1 | Accessory Conn. A1 | Accessory connection A1: 0 = Fan (continuous
operation); 1 = Venting valve, normally closed;
2 = Heating; 3 = Backing pump; 4 = Fan
(temperature controlled); 5 = Sealing gas; 6 =
always 0; 7 = always 1; 8 = Power failure
venting unit.
|
ACfgAccessoryConnA1 | UInt16 | EXPERT | RECONFIGURABLE | |
accessoryConnectionA2 | Accessory Conn. A2 | Accessory connection A2: 0 = Fan (continuous
operation); 1 = Venting valve, normally closed;
2 = Heating; 3 = Backing pump; 4 = Fan
(temperature controlled); 5 = Sealing gas; 6 =
always 0; 7 = always 1; 8 = Power failure
venting unit.
|
ACfgAccessoryConnA2 | UInt16 | EXPERT | RECONFIGURABLE | |
accessoryConnectionB1 | Accessory Conn. B1 | Accessory connection B1: 0 = Fan (continuous
operation); 1 = Venting valve, normally closed;
2 = Heating; 3 = Backing pump; 4 = Fan
(temperature controlled); 5 = Sealing gas; 6 =
always 0; 7 = always 1; 8 = Power failure
venting unit.
|
ACfgAccessoryConnB1 | UInt16 | EXPERT | RECONFIGURABLE | |
accessoryConnectionB2 | Accessory Conn. B2 | Accessory connection B2: 0 = Fan (continuous
operation); 1 = Venting valve, normally closed;
2 = Heating; 3 = Backing pump; 4 = Fan
(temperature controlled); 5 = Sealing gas; 6 =
always 0; 7 = always 1; 8 = Power failure
venting unit.
|
ACfgAccessoryConnB2 | UInt16 | EXPERT | RECONFIGURABLE | |
backingPump | Backing Pump | Operation mode backing pump: 0 = Continuous; 1
= Intermittend; 2 = Delayed switch on
|
AOperationModeBackingPump | UInt16 | EXPERT | RECONFIGURABLE | |
baudRate | Baud Rate | Baud Rate: 1=300 2=600 3=1200 4=2400 5=4800
6=9600 7=19200 8=38400 9=57600 10=115200 Baud.
|
ABaudRate | UInt8 | EXPERT | RECONFIGURABLE | |
bufferFull | Buffer Full | Buffer Full Notification.
|
ABufFull | Int16 | EXPERT | RECONFIGURABLE | |
configDO1 | Config. DO1 | Configure DO1: 0 = Rot. speed switch point
attained; 1 = No error; 2 = Error; 3 = Warning
4 = Error and/or warning; 5 = Set speed
attained; 6 = Pump on; 7 = Pump accelerates; 8
= Pumpe decelerates 9 = always 0; 10 = always
1; 11 = Remote priority active; 12 = Heating;
13 = Backing pump 14 = Sealing gas; 15 =
Pumping station
|
AConfigDO1 | UInt16 | EXPERT | RECONFIGURABLE | |
configDO2 | Config. DO2 | Configure DO2: 0 = Rot. speed switch point
attained; 1 = No error; 2 = Error; 3 = Warning
4 = Error and/or warning; 5 = Set speed
attained; 6 = Pump on; 7 = Pump accelerates; 8
= Pumpe decelerates 9 = always 0; 10 = always
1; 11 = Remote priority active; 12 = Heating;
13 = Backing pump 14 = Sealing gas; 15 =
Pumping station
|
AConfigDO2 | UInt16 | EXPERT | RECONFIGURABLE | |
configInputDI1 | Config. Input DI1 | Configure Input DI1: 0 = Deactivated; 1 =
Enable venting; 2 = Heating; 3 = Sealing gas; 4
= Run-up time control; 5 = Rotation speed
setting mode; 6 = Motor.
|
AConfigInputDI1 | UInt16 | EXPERT | RECONFIGURABLE | |
configInputDI2 | Config. Input DI2 | Configure Input DI2: 0 = Deactivated; 1 =
Enable venting; 2 = Heating; 3 = Sealing gas; 4
= Run-up time control; 5 = Rotation speed
setting mode; 6 = Motor.
|
AConfigInputDI2 | UInt16 | EXPERT | RECONFIGURABLE | |
configOutputA01 | Config Output A01 | Configure output AO1: 0 = Actual rotation
speed; 1 = Power; 2 = Current; 3 = always 0 V;
4 = always 10 V.
|
AConfigOutputAO1 | UInt16 | EXPERT | RECONFIGURABLE | |
controlInterface | Control Interface | Control interface: 1 = Remote; 2 = RS485; 4 =
PV.can; 8 = Field bus; 16 = E74; 255 = Unlock
interface selection.
|
AControlViaInterface | UInt16 | EXPERT | RECONFIGURABLE | |
dataFrame | Data Frame | Data Frame: 1=7E1 2=7O1 3=8N1 4=8E1 5=8O1 9=7E2
10=7O2 11=8N2 12=8E2 13=8O2.
|
ADataFrame | UInt8 | EXPERT | RECONFIGURABLE | |
drivePower | Drive Power | Drive power.
|
ADriverPower | UInt32 | EXPERT | READONLY | |
driveUnitName | Drive Unit Name | Name of the electronic drive unit.
|
ANameDriveUnit | String | EXPERT | READONLY | |
enableFifoCont | Enable FIFO Cont. | Enable send FIFO data continuous
|
AFifoCont | Bool | EXPERT | RECONFIGURABLE | |
enableRtsCts | Enable RTS/CTS | Enable RTS/CTS
|
ARtsCts | Bool | EXPERT | RECONFIGURABLE | |
enableTransferOpt | Enable Transfer Rate Opt. | Enable transfer rate optimization
|
ATransferOpt | Bool | EXPERT | RECONFIGURABLE | |
enableVenting | Enable Venting | Enable venting.
|
AEnableVenting | Bool | EXPERT | READONLY | |
enableXonXoffRx | Enable XOn/XOff Rx | Enable XOn/XOff supported rx data
|
AXonXoffRx | Bool | EXPERT | RECONFIGURABLE | |
enableXonXoffTx | Enable XOn/XOff Tx | Enable XOn/XOff supported tx data
|
AXonXoffTx | Bool | EXPERT | RECONFIGURABLE | |
errorAck | Error Ack | Error Acknowledgment.
|
AErrorAck | Bool | EXPERT | RECONFIGURABLE | |
errorCodeHistory1 | Err Code History 1 | Error code history 1.
|
AErrorCodeHistory1 | String | EXPERT | READONLY | |
errorCodeHistory10 | Err Code History 10 | Error code history 10.
|
AErrorCodeHistory10 | String | EXPERT | READONLY | |
errorCodeHistory2 | Err Code History 2 | Error code history 2.
|
AErrorCodeHistory2 | String | EXPERT | READONLY | |
errorCodeHistory3 | Err Code History 3 | Error code history 3.
|
AErrorCodeHistory3 | String | EXPERT | READONLY | |
errorCodeHistory4 | Err Code History 4 | Error code history 4.
|
AErrorCodeHistory4 | String | EXPERT | READONLY | |
errorCodeHistory5 | Err Code History 5 | Error code history 5.
|
AErrorCodeHistory5 | String | EXPERT | READONLY | |
errorCodeHistory6 | Err Code History 6 | Error code history 6.
|
AErrorCodeHistory6 | String | EXPERT | READONLY | |
errorCodeHistory7 | Err Code History 7 | Error code history 7.
|
AErrorCodeHistory7 | String | EXPERT | READONLY | |
errorCodeHistory8 | Err Code History 8 | Error code history 8.
|
AErrorCodeHistory8 | String | EXPERT | READONLY | |
errorCodeHistory9 | Err Code History 9 | Error code history 9.
|
AErrorCodeHistory9 | String | EXPERT | READONLY | |
firmwareVersion | Firmware Version | Firmware version drive unit.
|
AFirmwareVersDriveUnit | String | EXPERT | READONLY | |
gasMode | Gas Mode | Gas Mode: 0 = Heavy; 1 = Light; 2 = Helium.
|
AGasMode | UInt16 | EXPERT | RECONFIGURABLE | |
heatingOnOff | Heating On/Off | Heating On/Off.
|
AHeating | Bool | EXPERT | READONLY | |
hwVersionDriveUnit | HW Version | Hardware version of electronic drive unit.
|
AHWVersionDriveUnit | String | EXPERT | READONLY | |
interfaceSelectionLocked | Lock Interface Selection | Lock interface selection.
|
AInterfaceSelectionLocked | Bool | EXPERT | RECONFIGURABLE | |
motorPump | Motor Pump | Motor pump.
|
AMotorPump | Bool | EXPERT | READONLY | |
nominalRotationSpeed | Nominal Rot. Speed | Nominal rotation speed.
|
ANominalSpeed | UInt32 | EXPERT | READONLY | |
nominalRotationSpeedConfirmation | Nominal Rot. Speed Confirmation | Confirmation of nominal rotation speed.
|
ANominalRotSpdConfirmation | UInt32 | EXPERT | RECONFIGURABLE | |
nominalRotationSpeedRpm | Nominal Rot. Speed | Nominal rotation speed [rpm].
|
ANominalSpeedrpm | UInt32 | EXPERT | READONLY | |
operatingHoursDriveUnit | Operating Hours Drive Unit | Operating hours drive unit.
|
AOperatingHourDriveUnit | UInt32 | EXPERT | READONLY | |
operatingHoursPump | Operating Hours Pump | Operating hours pump.
|
AOperatingHoursPump | UInt32 | EXPERT | READONLY | |
overtTempDriveUnit | Over Temp Drive Unit | Over temperature drive unit.
|
AOverTempDriveUnit | Bool | EXPERT | READONLY | |
overtTempPump | Over Temp Pump | Over temperature pump.
|
AOverTempPump | Bool | EXPERT | READONLY | |
powerConsumptionValue | Power Consumption Value | The value of power consumption.
|
AValuePowerConsumption | UInt16 | EXPERT | RECONFIGURABLE | |
pumpAccelerates | Pump Accelerates | Pump accelerates.
|
APumpAccelerates | Bool | EXPERT | READONLY | |
pumpCycles | Pump Cycles | Pump cycles.
|
APumpCycles | UInt32 | EXPERT | READONLY | |
pumpingStationOnOff | Pumping station On/Off | Pumping station On/Off.
|
APumpingStation | Bool | EXPERT | READONLY | |
rotationSpeedDelayedVenting | Venting Rot. Speed @ Delayed Venting | The venting rotation speed at delayed venting.
|
AVentRotSpdDelayedVenting | UInt16 | EXPERT | RECONFIGURABLE | |
rotationSpeedSettingMode | Rotation Speed Set Mode | Rotation speed setting mode: 0 = Off; 1 = On.
This setting is needed for Standby operation.
|
ARotSpeedSettingMode | UInt16 | EXPERT | RECONFIGURABLE | |
rotationSpeedSettingModeValue | Rot. Speed Setting Mode Value | The value of the rotation speed setting mode.
|
AValueRotSpdSettingMode | Float | EXPERT | RECONFIGURABLE | |
rotationSpeedStandBy | Rot. Speed Stand-By | The rotation speed at stand-by.
|
ARotationSpeedStandby | Float | EXPERT | RECONFIGURABLE | |
rotationSpeedSwitchPointAttained | Rot. Speed Switchpoint Attained | Rotation speed switch point attained.
|
ARotationSpdSwPtAttained | Bool | EXPERT | READONLY | |
rotationSpeedSwitchpoint | Rot. Speed Switch Point | Rotation speed switch point: 0 = switch point 1
only; 1 = switch points 1 and 2.
|
ACfgRotationSpeedSwitchpoint | UInt16 | EXPERT | RECONFIGURABLE | |
rotationSpeedSwitchpoint1 | Rot. Speed Switch Point 1 | The rotation speed switch point 1.
|
ARotSpdSwitchPoint1 | UInt32 | EXPERT | RECONFIGURABLE | |
rotationSpeedSwitchpoint2 | Rot. Speed Switch Point 2 | The rotation speed switch point 2.
|
ARotSpdSwitchpoint2 | UInt32 | EXPERT | RECONFIGURABLE | |
rs485DeviceAddress | RS485 Device Address | The address of the RS485 device.
|
ARS485DeviceAdress | UInt32 | EXPERT | RECONFIGURABLE | |
runUpTimeOnOff | Run-Up Time | Run-up time control
|
ARunUpTimeControl | Bool | EXPERT | RECONFIGURABLE | |
sealingGasOnOff | Sealing Gas | Sealing gas On/Off.
|
ASealingGas | Bool | EXPERT | RECONFIGURABLE | |
serialCheck | Serial Check | Check serial protocol command value (reads back
string from command function window (ASerP
input value)
|
ASerCheck | String | EXPERT | RECONFIGURABLE | |
serialString | Serial String | Send serial string.
|
ASerial | String | EXPERT | RECONFIGURABLE | |
setRotationSpeed | Set Rot. Speed | Set rotation speed.
|
ASetRotSpeed | UInt32 | EXPERT | READONLY | |
setRotationSpeedRpm | Set Rot. Speed | Set rotation speed [rpm].
|
ASetRotSpeedrpm | UInt32 | EXPERT | READONLY | |
setSpeedAttained | Set Speed Attained | Set speed attained.
|
ASetSpeedAttained | Bool | EXPERT | READONLY | |
switchOffThresholedBKP | Switch Off Threshold BKP | Switching off threshold backing pump in
intermittent mode.
|
ASwoffThresholdBKP | UInt16 | EXPERT | RECONFIGURABLE | |
switchOnThresholedBKP | Switch On Threshold BKP | Switching on threshold backing pump in
intermittent mode.
|
ASwonThresholdBKP | UInt16 | EXPERT | RECONFIGURABLE | |
targetRunupTime | Set Value Run-Up Time | The run-up time set value.
|
ASetValueRunUpTime | UInt32 | EXPERT | RECONFIGURABLE | |
temperaturePumpBottom | Temp Pump Bottom | Temperature pump bottom part.
|
ATemperaturePumpBottom | UInt32 | EXPERT | READONLY | |
ventingMode | Venting Mode | Venting mode: 0 = Delayed Venting; 1 = No
Venting; 2 = Direct Venting.
|
AVentingMode | UInt16 | EXPERT | RECONFIGURABLE | |
ventingTimeDelayedVenting | Venting Time @ Delayed Venting | The venting time at delayed venting.
|
AVentTimeDelayedVenting | UInt32 | EXPERT | RECONFIGURABLE |